Check the phase sequence relay price in Pakistan for the CNC Electric XJ3-D three-phase protection relay. The XJ3-D keeps a three-phase motor from running with a missing phase or the wrong phase order. It watches the supply and controls the contactor coil circuit to stop unsafe starts.
Key Features
- Operating voltage AC 380V, 50/60Hz
- Over-voltage window 380–460V, delay 1.5–4s adjustable
- Under-voltage window 300–380V, delay 2–9s adjustable
- Phase failure and sequence reaction ≤2 seconds
- 1 changeover contact; AC-15 380V / 0.47A; Ith 3A
- Electrical life 1×10⁵ operations
Technical Specifications
| Product listing | 3 Phase Sequence Relay | Reliable Phase Protection & Monitoring |
|---|---|
| Model sold locally | XJ3-D |
| Protection functions | Overvoltage, undervoltage, phase failure, phase sequence error |
| Operating voltage | AC 380V, 50/60Hz |
| Overvoltage range | 380V to 460V, 1.5s to 4s adjustable |
| Undervoltage range | 300V to 380V, 2s to 9s adjustable |
| Phase failure / sequence reaction time | ≤2 seconds |
| Contact form | 1 group changeover contact |
| Contact capacity | Ue/Ie AC-15 380V / 0.47A; Ith 3A |
| Electrical life | 1×105 operations |
| Mechanical life | 1×106 operations |
| Ambient temperature | -5°C to +40°C |
| Installation mode | 35mm rail installation or soleplate mounting |
Where to Use
- Pumps, compressors and chillers
- Lifts and textile machines
- Workshop control panels
How to Choose
Wire its changeover contact into the contactor coil circuit so the motor stops when a fault is detected.
Phase Sequence Relay Price in Pakistan
The current price in Pakistani rupees is shown at the top of this page, together with the stock status, so you can order with confidence.
Frequently Asked Questions
What faults does it detect?
Phase failure, wrong phase sequence, over-voltage and under-voltage.
Can the voltage limits be adjusted?
Yes, with adjustable delay windows.
How does it stop the motor?
By controlling the contactor coil circuit.












There are no reviews yet.